How can we help you today?

What is the cable pinout (RJ45 to RJ45) to connect a Compact 258/265/275/285 PLC to a 174CEV30010/20?

Issue

A serial communication cable is required between a Compact 258/265/275/285 and a CEV 300 10/20.

Product Line

  • Compact 258/265/275/285
  • CEV 300 10/20

Resolution

Wire the cable according to the following pinout:

Compact 258/265/275/285SignalConnectionCEV 300 10/20Signal
Pin 1+5 V→Pin 2DTR
Pin 2DSR→Pin 1NC
Pin 3TX→Pin 3RX
Pin 4RX→Pin 4TX
Pin 5GND→Pin 5GND
Pin 8Chassis GND→Pin 8NC

In addition:

  • On the Compact 258/265/275/285 side, bridge pin 6 (RTS) and pin 7 (CTS).
  • On the CEV 300 10/20 side, bridge pin 6 (CTS) and pin 7 (RTS).

pinout, compact 258



Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings