Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can you install a 2 pole breaker in a NQSFB2HJ?

Issue:
Use 2 and 3 pole breakers in the NQSFB2HJ subfeed breaker kit

Product Line:
Panelboards

Environment:
NQ

Cause:
Application with 2 or 3p breakers

Resolution:
This kit is only to be used with 3p H or J frame breakers, not 2p.
See Instruction Bulletin  80043-730-01 for clarification.

https://www.se.com/us/en/download/document/80043-730-01/

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings