How can we help you today?
Is it possible to measure the B phase current in a 3-Wire Delta system using a CM-2000 series meter?
Issue
Product Line
CM-2000 Series Meters
Environment
Metering Installation and Configuration
Cause
End User has inquired about whether or not a CM2000 can measure B Phase Current in a 3-Wire Delta System.
Resolution
The CM-2000 does not support a 3 CT configuration for 3-Wire Delta systems. The B phase is calculated regardless of whether you use 2 CT's or 3 CT's on a CM-2000 connected to a 3-Wire Delta system.
The appropriate system type for a 3-Wire Delta system is type 30 which requires 2 PTs and 2 CTs. Documentation for the CM2000 meter can be found here.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.