How can we help you today?
Can the split core current transformer (CT) cables be extended on the Split-Core Branch Current Monitor (BCMSC) meter?
Issue:
The end user would like to extend the length of cables attached the a Current Transformer on a BCMSC meter.
Product Line:
Branch Current Monitor Split Core (BCMSC)
Environment:
Current Transformer for BCMSC
Cause:
The monitoring source may be beyond reach of the Current Transformer that comes standard with the BCMSC.
Resolution:
The split core current transformers can be extended to a maximum distance of 20 feet. The recommended wire size is 10 gauge (AWG).
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.