How can we help you today?
Is there a script in Vijeo Designer that will allow me to write a new IP address of an Equipment at Runtime?
Issue:
Writing a new IP address of an Equipment at Runtime in Vijeo Designer
Product Line:
Vijeo Designer
Resolution:
Yes, you can write the IP address of an equipment via scripting. This feature was implemented in Vijeo Designer V5.0 SP1. This code will set IP Addresses for any driver, not just the Modbus driver. Below is an example script:
// --------------- Write some data -----------------------------------------// Length is given by NewIP_InputData.length
-
- int [ ] NewIP_InputData = {10, 187, 225, 135};
ModbusEquipment01.openConfig();
ModbusEquipment01.setProperty( "Con_IPAddress", NewIP_InputData );
ModbusEquipment01.commitConfig();
- int [ ] NewIP_InputData = {10, 187, 225, 135};
-
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.