Do You Need to Remove the Factory Jumpers on Altivar ATV61/ATV71 Drives?

Resolution:

Altivar ATV61 and ATV71 drives are shipped with two factory-installed jumpers. In normal applications, these jumpers should remain in place. They are only removed in specific, intentional use cases.

PA/PO Jumper (DC Bus)

  • Default: Leave installed. The jumper connects the internal DC bus as designed.
  • When to remove: Only if an external DC choke is installed.
    In this case, the choke replaces the jumper connection.
  • Important: If the jumper is removed, the terminal screws must still be fully tightened due to high current flow in this circuit.

PWR / +24 VDC Jumper (Power Removal Function)

  • Default: Leave installed. This allows the drive to operate normally.
  • When to remove: When integrating a safety circuit, such as:
    • An emergency stop (E-stop)
    • A shutdown circuit using a normally closed, dry contact
  • Removing this jumper allows the Power Removal safety function to disable motor operation when the safety circuit opens.


Summary

  • Do not remove jumpers for standard installations
  • Remove PA/PO only when adding a DC choke
  • Remove PWR/+24 VDC only when implementing a safety or E-stop circuit

.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.