How can we help you today?

Can I change the trip unit of the Powerpact H, J and L frame circuit breakers which are equipped with an I-Line jaw assembly for installation in I-Line panelboard and QED I-Line distribution sections?

Issue:
Change the trip unit of the Powerpact H, J and L frame circuit breakers for installation in I-Line panelboard and QED I-Line distribution sections

Product Lines:
Panelboards and Switchboards

Environment:
UL 67, UL 50, CSA C22.2 No.'s 29 and 94 -1989, NEMA PB1, NFPA 70 Art. 408, Federal Specification W-P-115C Type 1 Class 1, UL891

Cause:
Changing a trip unit, when possible, can be less costly and more convenient than obtaining a new circuit breaker.

Resolution:
No, the presence and necessity of the mounting foot on the I-Line version of these circuit breakers excludes the capability of changing the trip unit.
This is the case for thermal-magnetic versions as well as versions with Micrologic trip units.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings