Is the indicator button on the GFM's and ELM's an indicator only or does it need to be reset to provide protection?
Issue:
Is the indicator button on the GFM's and ELM's an indicator only or does it need to be reset to provide protection?
Product Line:
GFM and ELM
Resolution:
The ground fault indicator button is indication only, and does not need to be reset to provide protection. However, the intention is to reset the indictor when you close the breaker to be ready for the next fault indication.
Is the indicator button on the GFM's and ELM's an indicator only or does it need to be reset to provide protection?
Product Line:
GFM and ELM
Resolution:
The ground fault indicator button is indication only, and does not need to be reset to provide protection. However, the intention is to reset the indictor when you close the breaker to be ready for the next fault indication.