What is the function of the OIL parameter of an ATS48 series soft starter and how do I configure it?
Issue:
OIL parameter configuration of an ATS48 series soft starter
Resolution:
The OIL (Current Overload Activation) parameter in an ATS48 soft starter provides an optional current-based alarm or fault function. It allows you to trigger an alarm or stop the motor when the current exceeds a user-defined threshold.
By default, OIL is set to OFF and does not need to be configured unless a custom current limit is required.
Note: The OIL function is separate from the ATS48's Thermal Overload Protection. It is intended for application-specific current monitoring rather than motor thermal protection.
Configure a Custom Current Alarm or Fault
-
Set OIL to:
- DEF = Generates a fault and stops the motor.
- ALA = Generates an alarm only.
-
Set LOC to the desired current threshold.
- Adjustable from 50% to 300% of the motor's nominal current (IN).
-
Set IN (in the SET menu) to the motor's full-load current (FLC).
-
Set TOL to define how long the current can remain above the LOC threshold before the alarm or fault is triggered.
Example: Conveyor Jam Protection
A conveyor is driven by a motor rated at 100 A full-load current, but normal operation never requires more than 80 A. If current exceeds 80 A, it may indicate a jam or mechanical problem.
Configure the parameters as follows:
SET Menu
- IN = 100 A
PRO Menu
- OIL = DEF
- LOC = 80%
- TOL = 5 s
With these settings, the soft starter will trip on an OLC fault and stop the motor if the current exceeds 80 A for more than 5 seconds.
Alarm-Only Configuration
If you want a warning without stopping the motor:
- Set OIL = ALA
- Assign Relay Output R3 = AIL
In this configuration, the soft starter activates an alarm when the current threshold is exceeded, while allowing the motor to continue running.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.