What is the force required to open and close the operating handle of a heavy duty safety switch?

Issue:
Handle force to turn a switch ON or OFF

Product Line:
Heavy Duty Safety Switch

Resolution:
The handle for required to turn a heavy duty safety switch on and off are as follows:
30 A, Series F = 7.6 lbs on; 6.5 lbs off
60 - 100 A, Series F = 9.7 lbs on; 8.3 lbs off
200 A, Series F = 15.7 lbs on; 16.8 lbs off
400 - 600 A, Series E = 36.2 lbs on; 33.0 lbs off
800 - 1200 A, Series E = 54.2 lbs on; 53.6 lbs off