How do you select the input type (analog, thermocouple, PT100, RTD) on the Zelio REG24 Temperature Controllers?

Issue:
Selection of input type on Zelio REG24 Temperature Controllers?

Product Line:
Relays and Timers

Environment:
Zelio Speed, Frequency, & Temperature Control Relays

Resolution:
Accessing the parameter
1.     Press the SEL key until P is displayed.
2.     Press the Down Arrow key until P-n2 is displayed.
3.     Press the SEL key.
6.     Change the value from the default  to one of the following using the Arrow keys.

Value: Input Type

1 (PT 100 Ω )
2 (J)
3 (K)
4 (R)
5 (B)
6 (S)
7 (T)
8 (E)
12 (N)
13 (PL-2)
16 (1 VDC...5 VDC)
16 (4 mA...20 mA)