Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What is the minimum size terminal required for the QOU and QOUR breakers with ring terminations?
Issue:
What is the size of the terminal ring blade that will fit in a QOUR breaker?

Product Line:
Circuti Breaker

Resolution:
Use single UL Listed or CSA Certified insulated ring terminal or standard barrel tongue lug only. Must be suitable for 10-32 x 3/8 in. screw, provided. Tongue lug must be insulated.
NOTE: Some manufacturers’ terminals will be too wide to fit. Terminal ring blade must be under 0.44 in. (11.2 mm) wide.

Here is the instruction bulletin 48840-218-01.