Why might an ATV212 Drive always run at the low speed setting and not follow the analog input signal?
Resolution:
The low speed setting is parameter LL.
Verify that the VFD is setup to look for the analog input:
DIP switch SW100 position VIA at U (voltage) or I (current), VIB at U (voltage)
Frequency mode select, FMOd:
1 = VIA input
2 = VIB input
Verify the analog input signal by measuring the mA or Vdc on VIA / VIB. Also check polarity, (+) on VIA / VIB and (- ) on CC.
Logic input R has factory default assignment as preset speed, F112 = 6, Sr1 = 15Hz. If R is active, the VFD will run at 15Hz or LL (low limit) only. Check / correct the R input status and assignment. Note that in an S-Flex product, R is a run permissive input, F112 = 1. If a replacement ATV212 is installed or the VFD was reset to factory defaults, reprogram the VFD per the S-Flex manual.
Verify that the PID parameter, F360, is set correctly:
0 = no PID control
1 = PID per VIA feedback
2 = PID per VIB feedback
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.