Video: How do you set up PID control on the ATV21 and ATV212 drives?
Resolution:
- Press the mode button until you see AUF
- Arrow down to F------ and press enter
- Find F360 and press enter choose your PID feedback assignment and to activate your PID function
- 1 for VIA
- 2 for VIB
- Set to 3 if you want to use the up and down arrows as your set point.
- Set to 1 for VIA or 2 for VIB if you want your analog input to be your set point.
Please note: it is not a good idea to set up to set your PID feedback F360 to 1 VIA and your set point FNOD to 1 VIA.
Basic setup for a 4-20mA signal input for PID feedback would be:
F201=20% (4mA)
F202=0
F203=100% (20mA)
F204= 60hz
F360= 1 (enable PID and feedback is VIA 4 to 20mA)
FNOD= 3 (up and down arrows are your set point.
Optional settings:
F362=PID proportional gain
F363= PID integral gain
F380 = 1 for Reverse acting (0 = deactivated)
Ref manual 30072-451-63
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.