Video: Increasing Starting Torque on the ATS22

Increasing the parameters below can help deliver more breakaway torque, allowing the motor to begin turning and accelerate to speed more effectively.

SET Menu

T90 – Initial Voltage
Controls the initial voltage applied during startup. Adjustable from 10% to 50% of full voltage in 5% increments.
Factory setting: 30%.

ILt – Current Limit
Defines the maximum current permitted during motor startup. Adjustable up to 700% of the Motor Rated Current (In), with an upper limit of 350% of the Soft Starter’s rated current (IcL).
Factory setting: 350%.


ADJ Menu

(Note: To access the ADJ menu, set the LAC parameter in the SET menu to “on.”)

bSt – Boost Time
Applies an 80% voltage pulse (based on the Line Voltage UIn) for 0.0 to 1.0 seconds to help overcome initial static friction.
Factory setting: 0.0 seconds.



If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.