How do you set up preset speeds on the ATV32 drives?

Article available in these languages: Spanish

Issue:
Preset speeds configuration on the ATV32 drives

Product Line:
Altivar ATV32

Environment:
All

Cause:
Preset speeds for controlling the speed

Resolution:
FULL menu enter
FUn menu enter
PSS menu enter
PS2= 2 preset speeds assign to your logic input
PS4= 4 preset speeds assign to your logic input
PS8= 8 preset speeds assign to your logic input
PS16= 16 preset speeds assign to your logic input

Preset speed values are  SP2 thru SP16 in hz.

Example 3 speeds you will need to assign 4 preset speeds
LI4  preset 2 preset speeds
LI5 preset 4  preset speeds

Logic will be as follows
LI4=0 LI5=0  Drive runs at low speed for follows your analog input.
LI4=1 LI5=0 Drive runs at speed 2
LI4=0 LI5=1 Drive runs at speed 3
LI4=1 LI5=1 Drive runs at speed 4





Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings