What solid neutral kits can be used with the L600AWK circuit breaker enclosures?
Issue:
Application
Product Line:
Circuit Breaker Enclosure
Resolution:
There are several options for solid neutral kits for use with the L600AWK:
SN400LA for up to 400 A applications. Accepts Al or Cu conductors
SNC400LX for up to 400 A applications. Accepts only Cu conductors
SN1000MA for up to 600 A applications. Accepts Al or Cu conductors
SNC800LX for up to 600 A applications. Accepts only Cu conductors
For Ground Fault Breaker Applications:
SN600LXCT for up to 600 A applications. Accepts only Cu conductors and requires the use of the neutral current transformer (purchase neutral CT separately, S432575)
NOTE: No 200% rated neutral is available for the L600AWK
Application
Product Line:
Circuit Breaker Enclosure
Resolution:
There are several options for solid neutral kits for use with the L600AWK:
SN400LA for up to 400 A applications. Accepts Al or Cu conductors
SNC400LX for up to 400 A applications. Accepts only Cu conductors
SN1000MA for up to 600 A applications. Accepts Al or Cu conductors
SNC800LX for up to 600 A applications. Accepts only Cu conductors
For Ground Fault Breaker Applications:
SN600LXCT for up to 600 A applications. Accepts only Cu conductors and requires the use of the neutral current transformer (purchase neutral CT separately, S432575)
NOTE: No 200% rated neutral is available for the L600AWK
Released for: Schneider Electric USA
Explore more
Category:
Explore more
Category:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.