Does Unity Pro/Control Expert include state ram when importing a ProWORX project?
Issue
When opening/importing a ProWORX project which included State ram into Unity Pro/Control Expert is the state ram included?
Product Line
Unity Pro, ProWORX
Resolution
Yes. State ram addresses are brought in as variables, often as unused arrays . The naming syntax is as follows;
400001 would be seen in the Variable Editor as _400001 located to %MW1.
000001 would be seen as _00001 located to %M1.
100001 would be seen as _10001 located to %I1.
300001 would be seen as _30001 located to %IW1.
These values can be seen online to the CPU or the simulator by displaying them in the Animation Table.
***If you do not see the state ram values after loading the project, make sure that 'Initialize %MWi' is checked on the CPU configuration page before transferring.***
Yes. State ram addresses are brought in as variables, often as unused arrays . The naming syntax is as follows;
400001 would be seen in the Variable Editor as _400001 located to %MW1.
000001 would be seen as _00001 located to %M1.
100001 would be seen as _10001 located to %I1.
300001 would be seen as _30001 located to %IW1.
These values can be seen online to the CPU or the simulator by displaying them in the Animation Table.
***If you do not see the state ram values after loading the project, make sure that 'Initialize %MWi' is checked on the CPU configuration page before transferring.***
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.