How Can I Safely Simulate a Fault on an Altivar Drive to Test Redundant System Operation?
Resolution:
Recommended Methods:
Method 1: Output Phase Loss Simulation (Preferred)
This method creates a fault without risking damage to equipment.
- Power down the drive.
- Disconnect the motor leads from all three drive output terminals.
- Verify that Output Phase Loss monitoring is enabled on the drive
(parameter location varies by model — refer to the drive’s programming manual). - Issue a RUN command with the motor disconnected.
Result:
The drive will detect an output phase loss and generate a fault.
Common fault codes may include OPF, OPF2, EPHO, or similar, depending on the drive model.
Method 2: External Fault via Logic Input
- Assign an External Fault function to a logic input.
- Trigger the input using a momentary contact closure.
Result:
The drive will immediately fault, allowing you to confirm fault detection and system switchover behavior.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.