What is the torque for attaching the main lugs to the bus on a 225 Amp Main Lug Only NQ panel?
Issue:
Torque spec for NQ panel
Product Line:
Panelboards
Environment:
NQ
Resolution:
Use 25-30 ft. lbs or 275 lbs-in. This information can be found on the label behind the panel dead-front.
See attached copy of the label.
Torque spec for NQ panel
Product Line:
Panelboards
Environment:
NQ
Resolution:
Use 25-30 ft. lbs or 275 lbs-in. This information can be found on the label behind the panel dead-front.
See attached copy of the label.