What can cause an SCF2 (Impedant short circuit) fault on the ATV61 and ATV71 drives?

Article available in these languages:

  • Spanish

Issue:
Causes for SCF2 fault on the ATV61/ATV71 drives.

Resolution:

  1. Check the motor and motor cables
    • Disconnect the motor from the drive.
    • Test the motor cables and motor insulation using a 1 kV megohmmeter (Megger).
  2. Check motor grounding
    • Verify that the motor is properly grounded.
    • Confirm that a ground conductor is connected directly between the drive and the motor.
  3. Check the switching frequency
    • Verify the drive's switching frequency and adjust it if needed.
  4. Run the transistor diagnostic test
    • Go to [1.10 DIAGNOSTICS].
    • Run the Transistor Test using the drive's auto-diagnostics function.
  5. Consider the motor cable length
    • For long cable runs between the drive and motor, consider using a load reactor, dV/dt motor filter, or sine-wave filter.
  6. Test the VFD output
    • Disconnect the motor leads.
    • Disable Output Phase Loss detection.
    • Set the motor control type to V/F 2pts.
    • Run the drive at several frequencies, such as 20 Hz, 40 Hz, and 60 Hz.
    • At each frequency, measure the phase-to-phase output voltage across all three phases.
    • Compare the readings. The output voltages should be balanced within several volts.
Safety note: Perform insulation and voltage measurements only with appropriate electrical safety procedures and qualified personnel. Ensure the motor is disconnected from the drive before performing the 1 kV insulation test.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings