How Do You Wire and Configure a Dynamic Braking Resistor on Altivar Drives?

Resolution:

A dynamic braking (DB) resistor can be used with supported Altivar drives to improve deceleration performance and reduce stopping time.

Wiring

Connect the dynamic braking resistor to terminals PA and PB on the drive.

Programming

Altivar 31 (ATV31), Altivar 312 (ATV312), and Altivar 32 (ATV32)

  1. Navigate to FUN menu.
  2. Open the rPt submenu.
  3. Set brA (Brake Assignment) to NO.

Altivar 61 (ATV61) and Altivar 71 (ATV71)

  1. Navigate to Menu 1.7 – Application Functions.
  2. Open the Ramp submenu.
  3. Set Dec Ramp Adapt to NO.

Note: The Altivar Process ATV630 series is not designed for use with dynamic braking resistors.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.