How can we help you today?
What is the ATS22 adjustment range for parameter In, Motor Rated Current?
Issue:
Motor Rated Current adjustment range on the ATS22.
Product Line:
Altistart 22 ATS22
Environment:
All models
Cause:
What range of motors can be used for a particular ATS22 model
Resolution:
The Motor Rated Current, In, is adjustable from .4x to 1.0x the ATS22 current rating, IcL.
In other words, it can be adjusted down to 40% of the ATS22's rating.
Eg: An ATS22C17S6U, rated 170A, has an In range of 68 - 170A.
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.