What Happens to the Drive State When Deceleration Ramp Adaptation (bRA) Is Enabled on Altivar Drives?

Resolution:

When a stop command is issued, the drive enters the DEC (decelerating) state. This indicates that the motor speed is being reduced according to the configured deceleration ramp.

If the Deceleration Ramp Adaptation (bRA) function is enabled (set to YES), the drive may automatically increase the deceleration time if needed. This adjustment helps prevent issues such as DC bus overvoltage and ensures a safe, controlled stop.

  • The drive remains in the DEC state while the motor is slowing down—even if the ramp is being adapted.
  • Once the motor reaches zero speed, the drive transitions to the RDY (ready) state, indicating it is stopped and ready for the next command

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Attachment(s)

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.