What is the control power voltage for the ATSU01 soft starter?
Issue:
Control power voltage for the ATSU01 soft starter.
Product Line:
ATSU01
Cause:
Literature is conflicting.
Resolution:
The ATSU01 uses 24VDC control power only. It does not use 24VAC.