Can an Altivar 12 (ATV12) Drive Be Controlled from Both the Remote Display and the Terminal Inputs?

Resolution:

Yes. The Altivar 12 can be configured to accept run commands from both the remote display and a terminal input.

Configure the following parameters:

  • ConF → FULL → CtL → FR1 = LCC
  • ConF → FULL → CON → FLO = LIH

With this configuration:

  • The drive can be started from the remote display using the RUN button.
  • The drive can also receive a run command when the contact connected to LI1 is closed.

This setup allows control from the remote keypad while maintaining an external run command through the terminal input.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.