Are a neutral and neutral CT available for use with a PowerPacT L frame 400 - 600 A breaker installed in an L600AWK enclosure?

Issue:
Product Design Features

Product Line:
Circuit Breaker Enclosure

Resolution:
The L600AWK enclosure is suitable to accept the SN400LA, SNC400LX, SNC800LX, or the SN1000MA solid neutral assemblies.
When mounting the L Frame PowerPacT breaker with the LSIG function, the solid neutral with current transformer is required, so use the SN600LXCT (purchase neutral CT separately, part number S432575).