How can we help you today?

Why do I see 115 VAC on the outputs of the BMXDAO1605 when there is no load connected to to module?

Issue:

Why do I see 115 VAC on the outputs of the BMXDAO1605 when there is no load connected to to module?

Product Line:

BMXDAO1605

Resolution:

This is normal when attempting to measure a triac output with no load.  Triac outputs cannot be accurately tested without a load.
The high impedance of the voltmeter will introduce enough of a load to cause the applied voltage on the triac to be seen.
Test with a load applied to the triac and you'll get a more meaningful measurement.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.