What is the lug-mounting torque requirement for installing mechanical lugs to a Power Pact L frame breaker?
Issue:
Lug-mounting torque requirement for Power Pact L frame breaker
Product Line:
Circuit Breakers
Environment:
Powerpact L frame breaker.
Resolution:
The mounting screw torque for all mechanical lug kits to the Powerpact L frame breaker is 327 lb-in (37 N-m). This includes lug kits:
AL400L61K3
AL400L61K4
AL600LS52K3
AL600LS52K4
AL600LF52K3
CU400L61K3
CU400L61K4
CU600LS52K3
CU600LS52K4
CU600LF52K3
Note that this is different from the wire binding screw torque.
Wire binding screw torque is 442 lb-in (50 N•m) for all lug kits except for CU400L61K3 and CU400L61K4, which take 275 lb-in (31 N•m).
Note also that the torque requirements are the same if these lugs are applied to Compact NSJ and Powerpact D frame breakers.
Lug-mounting torque requirement for Power Pact L frame breaker
Product Line:
Circuit Breakers
Environment:
Powerpact L frame breaker.
Resolution:
The mounting screw torque for all mechanical lug kits to the Powerpact L frame breaker is 327 lb-in (37 N-m). This includes lug kits:
AL400L61K3
AL400L61K4
AL600LS52K3
AL600LS52K4
AL600LF52K3
CU400L61K3
CU400L61K4
CU600LS52K3
CU600LS52K4
CU600LF52K3
Note that this is different from the wire binding screw torque.
Wire binding screw torque is 442 lb-in (50 N•m) for all lug kits except for CU400L61K3 and CU400L61K4, which take 275 lb-in (31 N•m).
Note also that the torque requirements are the same if these lugs are applied to Compact NSJ and Powerpact D frame breakers.
Released for: Schneider Electric USA
Explore more
Category:
Explore more
Category:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.