What parameter activates Catch on the Fly on the ATV21 and ATV212 series drives and how is it configured?
Issue:
ATV21 and ATV212 parameter that activates Catch on the Fly
Product Line:
ATV21 and ATV212 drives.
Resolution:
Parameter F301 is used to configure the Catch on the Fly function. It has 5 possible settings:
0 : Deactivated
1 : Activated after brief power loss
2: Activated after run permissive is restored
3: Activated after a brief power loss or when run permissive is restored.
4: Activated at every startup.
“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.