Why won’t the ATV212 drive start when the P24–F run contact is closed?
Resolution:
If the ATV212 does not start when the P24–F run contact is closed, verify the following:
- Confirm that CMOd is set to 0 to enable terminal control.
- If any network functions are enabled for monitoring purposes, set F108 = 48.
- Review the logic input programming. Typically, F111 = 2 is used for the Run Forward function. Be aware that other settings may combine the Run Forward command with additional functions.
- Verify that the VFD is in Remote mode. The LOC/REM button’s green LED on the keypad should be OFF.
- Check the VFD’s 24 VDC control power supply by measuring between P24 and CC.
- Confirm that the run command circuit is complete by measuring 24 VDC between F and CC.
- Ensure that the drive has a valid speed reference. The drive may be running at 0 Hz, which is indicated by a red RUN LED on the display.
- Verify that the run permissive condition is satisfied.
- If the display shows “OFF”, the run permissive has not been met.
- Note that “OFF” may be a normal indication if the run permissive becomes active at the same time the run command is issued.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.