ATV32, how can I configure an emergency stop that will still follow the deceleration ramp
Resolution:
Safe Stop 1 function can be used to initiate an emergency stop of the drive. This can only be configured using SoMove. The ramp-down time is defined by parameters SSrt and SSru. Note that this input should be externally latched as the drive will be allowed to start again once the emergency stop signal on the terminal assigned to safe stop 1 is removed.
For more information, please refer to the ATV32 Safety Integrated Functions manual, document number S1A45606.
http://download.schneider-electric.com/files?p_Reference=S1A45606&p_EnDocType=User guide&p_File_Id=556547554&p_File_Name=ATV32_Safety_Functions_Manual_EN_S1A45606_05.pdf