How to setup a PTC alarm without tripping the ATV61 drive?
Issue:
PTC alarm installation
Resolution:
PTC warning can be indicated via a relay output assigned to an Alarm Group.
Example for SW2 switch set to PTC, PTC connected to LI6, R2 indication, Alarm Group 1:
1.8 Fault Management
-> PTC Management - activates the PTC monitoring
-> LI6 = PTC Probe [PTCL] = Always
->Motor Thermal Prot - Inactivates the VFD internal I2T overload protection
->Overload Fault Mgt [OLL] = Ignore
1.5 Inputs/Outputs CFG
-> R2 Configuration - assign relay R2
->R2 Assignment [R2] = Alarm Grp1
-> Alarm Grp1 Definition - activate PTC alarm for the warning group
-> LI6 = PTC Alarm [PLA] = ON
Important note: When Overload Fault Mgt [OLL] = Ignore, the motor thermal protection by calculating the I2t is inactive. The drive will not provide motor overload protection based on motor current. Both functions can work at the same time by keeping Overload Fault Mgt [OLL] = Freewheel
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.