Customer needs a CM732E Replacement meter Socket Interior and an KCL34200 for CMM switchboard . Since the breaker is obsolete , what is required ?

Issue:
What can be done to replace parts for a CM732E CMM Meter socket when the Legacy KCL breaker has been obsoleted?

Product Line:
CMM Switchboard

Environment:
Maintenance

Cause:
Replacement

Resolution:
For the new replacement Powerpact J Breakers to be used a new CM732E meter socket, the following parts are needed:

(1)  CMUHWKIT adapter kit for the new breaker
(1)  CM6BKRCVR breaker cover (for 6 socket CMM section) or CM3BKRCVR (for 3 socket CMM section)
(1)  JJL36200  250AF/200AT Powerpact breaker

Schneider Electric USA