How do you size a full voltage bypass contactor for open atyle ATS48 soft starters?
Resolution:
The full voltage bypass contactor should be sized based on the motor full load current (FLA).
Additional considerations:
If a bypass mode contactor is installed in the field, you may also need to install a line isolation contactor.
It is recommended to include normally closed (NC) auxiliary contacts to interrupt the control power supply (CL1–CL2) to the soft starter when operating in full voltage bypass mode.
This ensures proper operation and protects the soft starter by removing control power when it is no longer in the circuit and avoid triggering faults in the SoftStarter due to the current flowing through the bypass contactor.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.