Form R for 9036 float switches - reverse action

Issue:

How can the action of a 9036 float switch be changed so that the contacts open on rise and close on fall?

Product Line:

9036D and 9036G switches:

Environment:

US product

Cause:

Different applications require different contact arrangements

Resolution:

The form code R when added to te end of a 9036D or 9036G part number will reverse the action of a float switch.  The standard action of a float switch is for contacts to close on rise.  A reverse action switch will open on rise.  This modification can be field installed on 9036DG switches only with part 9049A58.

Schneider Electric USA