How many Remote IO drops does an M580 PLC support?
Issue:
How many Remote IO drops does an M580 PLC support?
Product Line:
M580
Resolution:
M580 CPU | Max Remote I/O Drops
--------------------------------------------------------------------------------
BME P58 2040 | 8
BME P58 3040 | 16
BME P(H)58 4040 | 16
BME P(H)58 5040 | 31
BME P(H)58 6040 | 31
--------------------------------------------------------------------------------
A "Rack" is defined as a backplane which holds devices.
A "Drop" is defined as the rack which are connected to CPU as a node on the RIO network.
A Drop can contain multiple racks by use of the BMXXBE Rack Extenders.