How can we help you today?

Where can the Device Memory Info be found in SoMachine or Machine Expert?

In SoMachine 4.1, 4.2 or 4.3 or Machine Expert 1.1, 1.2 or 2.0 the Device Memory Info can be found by going to the Logic Builder window and then Devices tree window. In any of these windows right-click on My Controller (your controller part number) and select Device Memory Info...

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.