Can the FFTK be used to test M2C contacts and the Micrologic trip unit advanced functions and trip history?
Issue:
Using Full Function Test Kit to test M2C Programmable Contacts.
Product Line:
Powerpact and Masterpact breakers.
Resolution:
When using the M2CTEST special adapter, all advanced protections, logging of trips, logging of alarms, activation of alarms and incrementing of the contact wear counter are enabled during the secondary injection test.
This adapter enables trip unit and M2C/M6C functions the FFTK would normally disable and more closely simulating a primary injection test.
See attached instruction bulletin EAV34309 for more information.
Using Full Function Test Kit to test M2C Programmable Contacts.
Product Line:
Powerpact and Masterpact breakers.
Resolution:
When using the M2CTEST special adapter, all advanced protections, logging of trips, logging of alarms, activation of alarms and incrementing of the contact wear counter are enabled during the secondary injection test.
This adapter enables trip unit and M2C/M6C functions the FFTK would normally disable and more closely simulating a primary injection test.
See attached instruction bulletin EAV34309 for more information.
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.