How can we help you today?

What are the voltage, temperature and altitude tolerances for the Altivar 32/320 drive?

Issue:
Customer wants to know the temperature and altitude limitations for the ATV32/ATV320 drive.

Product line:
ATV32, Altivar 32, ATV320, Altivar 320

Environment:
All

Cause:
n/a

Resolution:
The voltage range for the M2 drives (200-240V) is 200V, minus 15% to 240V, plus 10%.
The voltage range for the N4 drives (380-480V) is 380V, minus 15% to 480V, plus 15%.

The temperature rating for all models is +14F to +122F (-10C to +50C), without derating (as long as the switching frequency is 4 kHz or less).

Optional derating is available from +122F to +140F (50C to 60C).  Consult the Installation manual for de-rating curves based on the temperature and switching frequency.

The maximum altitude the Altivar 32 can be installed without de-rating is up to 3300 feet (1000 meters).  De-rate the drive nominal current by each additional 330 feet (100m) up to a maximum ceiling of 10,000 feet (3000m).

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.