How to setup the ATV61 or ATV71 HMI keypad to monitor two parameters other than frequency reference in hertz on the display screen?
Issue:
How to setup the HMI keypad to monitor parameters other than frequency in hertz on the display screen.
Product Line:
ATV61/71 Drives
Environment:
All serial numbers for ATV61/71 Drives
Cause:
N/A
Resolution:
To setup the HMI keypad to display parameters other than frequency in the displays screen follow these steps:
1. In the main menu go to Menu 6 Monitoring Configuration.
2. In the Monitoring Configuration Menu go to Menu 6.2 Monitor Screen Type: Example Digital.
3. Then go to Parameter Selection.
4. You can now choose up to 2 parameters.
Note: These parameters will be shown on the screen before the Main Menu.
Only 2 parameters can be choosing at a time.

How to setup the HMI keypad to monitor parameters other than frequency in hertz on the display screen.
Product Line:
ATV61/71 Drives
Environment:
All serial numbers for ATV61/71 Drives
Cause:
N/A
Resolution:
To setup the HMI keypad to display parameters other than frequency in the displays screen follow these steps:
1. In the main menu go to Menu 6 Monitoring Configuration.
2. In the Monitoring Configuration Menu go to Menu 6.2 Monitor Screen Type: Example Digital.
3. Then go to Parameter Selection.
4. You can now choose up to 2 parameters.
Note: These parameters will be shown on the screen before the Main Menu.
Only 2 parameters can be choosing at a time.
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.