Will a SL400 fit on a 400A I line combo panelboard Main lugs interior to feed a separate NQ Main lugs interior?
Issue:
I-line combo panels accepts the SL400 subfeed lug kit to feed separate loads like another panel
Product Line:
Panels
Environment:
I-line combo Panel
Resolution:
The SL400 will fit in the I-line section to feed separate mounted panels or other loads but it cannot be used to feed the NQ or NF interior in the I-line panel unless it is the the
I-line combo panel with the dual NQ or NF interiors. And then only 1 of those panels can be fed from a branch or subfeed lug kit.
I-line combo panels accepts the SL400 subfeed lug kit to feed separate loads like another panel
Product Line:
Panels
Environment:
I-line combo Panel
Resolution:
The SL400 will fit in the I-line section to feed separate mounted panels or other loads but it cannot be used to feed the NQ or NF interior in the I-line panel unless it is the the
I-line combo panel with the dual NQ or NF interiors. And then only 1 of those panels can be fed from a branch or subfeed lug kit.