How can we help you today?

What are the part numbers for the replacement cooling fans for the ATV61 and ATV71 drives?

Issue:
ATV61 and ATV71 replacement part numbers for cooling fans

Product Line:
Altivar ATV61 and ATV71 open type drives

Environment:
All

Cause:
Needs a replacement cooling fan for the ATV61 and ATV71 drives.

Resolution:
See attachments

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.