In Okken, Rusty cutting edges of cable tie support 87176 & 87177 are visible to customer, How to avoid this problem and what is the solution?

The problem:

  • The cable tie supports 87176 & 87177 are usually made of pre-plated Galvanized Iron sheets (FTR00052 - DX51D+Z275-M-B-C), In some environmental conditions, the cutting egdes become quickly rusty and visible. The paint touch-up on these edges is not recommended.

Solution:

  • We have recommended to use the Steel sheet DC01, finishing the fabrication process, and then going for plating Fe/Zn8/C1. Which is mentioned in the attachment - HRB7180100
  • Hereby, we do not recommend to go for paint touch-up on the rusty edges or full painting of these parts due to the following reasons,
    • The painting or powder coating will make these parts non-conductive.  Inside the switchboard board we have to maintain the continuity between different sections for earthing purpose. (Non-earthing will lead to performance issues)
    • In Okken, these parts are not only to fix the cables but also to fix the protective earthing (PE) busbars, which are subjected to continuity and short circuit withstand.

Schneider Electric USA

Attachment(s)
HRB7180100.pdf [13.54 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings