How can we help you today?
What is the AL05 code shown on the ATV212?
Issue:
Looking for the AL05 code shown on the ATV212.
Product Line:
ALTIVAR 212, ATV212
Environment:
All
Cause:
Troubleshooting
Resolution:
AL05 is the alarm code display in case of a signal loss on an analog input.
Example on VIA in 4-20mA
FMOD = VIA
[4-20 mA loss] F644 = freewheel
[Loss of VIA] F633 = 20% --> 20% on F633 is for 4mA.
Start the drive with VIA higher than 4mA
--> The drive run and goes to the speed given by VIA.
If VIA signal is loose (VIA less than 4mA)
--> AL05 is display showing the 4-20mA loss is detected.
--> Then Drive is stopped in freewheel
If AL05 is display on your product :
- check the signal level on VIA
- then check F633 is set correctly
There is nothing in manual on this code.
Looking for the AL05 code shown on the ATV212.
Product Line:
ALTIVAR 212, ATV212
Environment:
All
Cause:
Troubleshooting
Resolution:
AL05 is the alarm code display in case of a signal loss on an analog input.
Example on VIA in 4-20mA
FMOD = VIA
[4-20 mA loss] F644 = freewheel
[Loss of VIA] F633 = 20% --> 20% on F633 is for 4mA.
Start the drive with VIA higher than 4mA
--> The drive run and goes to the speed given by VIA.
If VIA signal is loose (VIA less than 4mA)
--> AL05 is display showing the 4-20mA loss is detected.
--> Then Drive is stopped in freewheel
If AL05 is display on your product :
- check the signal level on VIA
- then check F633 is set correctly
There is nothing in manual on this code.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.