How can we help you today?

What do the breaker status flags on a Masterpact NW indicate?

Issue:
Why do the flags on a Masterpact NW indicate Charged and Not-OK when it is charged and open?

Product Line:
Air Circuit breakers

Resolution:
Breaker flags indicate whether or not the breaker is open or closed, whether the springs are charged or not, and if the breaker will close with a close command.
The flags will indicate charged and OK only if the following conditions are met:
  • Breaker is open and charged
  • Shunt trip (if present) is NOT energized
  • UVR (if present) is energized
  • There is no padlock in place
  • Keylock (if present) is in operable position
  • Other interlocks such as spring-discharge and rod/cable interlocks are satisfied

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings