How can we help you today?

How does the underload time delay work on the ATV12 drives?

Issue:
Underload time delay on the ATV12 drives.

Product Line:
Altivar ATV12

Environment:
All

Cause:
Wants to know the underload time delay works.

Resolution:
I/O menu page 53: The Application underload time delay ( ULt) is the time delay before the underload fault occurs. It is adjustable from 0 to 100 secs.
The Application Underload threshold is set to a certain percentage of the FLA of the motor  ( from 20 to 100 of the FLA) that you want the drive to fault.
I_O Input screen shot

:


Schneider Electric USA

Attachment(s)
Programming manual.pdf [9.6 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings