ATV-IMC" is always 00:00 01/01/2000 | Schneider Electric USA" /> Time in ATV71 keypad under "DriveMenu -> ATV-IMC" is always 00:00 01/01/2000 | Schneider Electric USA

How can we help you today?

Time in ATV71 keypad under "DriveMenu -> ATV-IMC" is always 00:00 01/01/2000

This is because time is not synchronised between ATV71 and IMC card.

To enable time synchronisation the following program line should be added to ATV_IMC_Start POU:
DriveFaultDatation(Activate:=TRUE );

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.