What can cause an OPF or Motor phase loss on the ATV312 drive?

Resolution:

The OPF (Output Phase Fault) indicates that the drive has detected a loss of current on one or more motor output phases. This fault is typically related to the motor, motor wiring, or output circuitry between the drive and the motor.

Common Causes

  • One or more motor output phases are disconnected or open.
  • Loose, damaged, or incorrectly wired motor connections.
  • A damaged motor winding causing an imbalance in motor current.
  • An undersized motor operating below the drive's motor phase loss detection threshold.
  • Excessive contact resistance due to loose terminals or deteriorated connections.
  • An output contactor opened while the drive was running.
  • Incorrect motor parameter settings, particularly the motor rated current.
  • A failed output IGBT or internal power stage issue within the drive.

Troubleshooting Steps

  1. Verify all motor power connections at both the drive and motor terminals.
  2. Inspect motor cables for damage, loose connections, or open conductors.
  3. Measure motor winding resistance and check for phase-to-phase balance.
  4. Confirm the motor nameplate data is correctly programmed in the drive.
  5. Ensure no contactors or disconnect devices are opening between the drive and motor while the drive is running.
  6. Test the motor and cable insulation using appropriate methods.
  7. If available, run the drive with a known-good motor to isolate the issue.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.