How to import SoMachine/Machine Expert - Basic symbols in Vijeo Designer?
Using SoMachine Basic in SoMachine Central
- You need to export your project as "SoMachine Basic project" (see attachment 1).
- In Vijeo designer:
- In the IO Manager, add the Modbus TCP/IP Driver and select Modbus Equipment.
- Write the IP Address of the M221 PLC and check the case IEC61131. You also need to select the Double word order (see attachment 2).
- Do a right click in "Variables”, select "Link Variables" and "*.SMPB" for file types, then select your project (see attachment 3).
- You can now select which symbols you want to import.
Using SoMachine/Machine Expert - Basic standalone
In Vijeo designer:
- In the IO Manager, add the Modbus TCP/IP Driver and select Modbus Equipment.
- Write the IP Address of the M221 PLC and check the case IEC61131. You also need to select the Double word order (see attachment 2).
- Do a right click in "Variables”, select "Link Variables" and "*.SMPB" for file types, then select your project (see attachment 3).
- You can now select which symbols you want to import.